• siron-fire-protection-sprinklers-header-400px

Concealed Sprinklers

 

We deliver a comprehensive package of Concealed Sprinklers such as the G5-56, F1FR, G4 and SWC with a short delivery time.

siron-fire-protection-sprinklers-standard-response-g5-56-300-sr

G5-56 Concealed Sprinkler

 

Specification 034 Rev F
Styles
Concealed Quick Response Sprinkler (UL)
Approvals
UL Quick Response
- FM Standard Response K80
- VdS Standard Response K80
- LPCB Standard Response K80

K Factor
G5-80 K115 R¾" RA3412
G5-56 K80 R½" RA3415
G5-42 K60 R½" RA3413
G5-28 K40 R½" RA3411


Also available with perforated cover plate. 19mm height adjustable.

DOWNLOAD BULLETIN
siron-fire-protection-sprinklers-quick-response-f1fr-ccp

F1FR QR EC CCP K115


Specification 151 Rev F

Styles
Concealed Quick Response Extended Coverage Sprinkler
Approvals
- UL
K Factor

- 80

 

Sprinkler Coverage up to 6.0 m x 6.0 m!

 

 

 

 

 

 

 

DOWNLOAD BULLETIN
siron-fire-protection-sprinklers-quick-response-g4-xlo-qrec

G4 XLO QREC K160

 

Specification 144 Rev G
Styles
Concealed Quick Response Extended Coverage Sprinkler
Approvals
- UL
K Factor
- 160


Quick Response (QR Extended Coverage)  up to 6,1m x 6,1m coverage for light hazard occupancies.

 

 

 

DOWNLOAD BULLETIN
siron-fire-protection-sprinklers-quick-response-swc-concealed-extended-coverage-horizontal-sidewall

SWC Concealed Extended Coverage Horizontal Sidewall

 

Specification 163 Rev G
Styles
-Concealed Quick Response Extended Coverage Horizontal Sidewall Sprinkler
Approvals
- UL
K Factor
- 115

 

Coverage up to 4,3 m x 7,9 m.

 

 

 

 

 

 

 

DOWNLOAD BULLETIN
siron-fire-protection-sprinklers-quick-response-g5-56-sr-4

"Sealing" Concealed Sprinklers


Specification 043 Rev B
Styles
-Concealed Quick Response Sprinkler (UL)
Approvals
-UL Quick Response
K Factor
G5-56 K80 R½" RA3415
- G5-42 K60 R½" RA3413
- G5-28 K40 R½" RA3411

 

The Sealing Cover plate is 19 mm adjustable. The Sealing Cover Plate QR is not interchangeable with the Sealing Cover Plate SR. For use in Cleanrooms, Dust-free environments and operating rooms, etc.

 

DOWNLOAD BULLETIN

Need more information?

Contact us directly by phone +31 53 750 30 44 for more information about Concealed Sprinklers. We are open from 9am — 6pm week days.

You can also fill out our online contact form, and we will call you as soon as possible.

Learn more about the system that suits your installation best.